DC Power

DC power pack

Poweris ELT

The Poweris ELT packs in chassis or in casing supply with back-up the equipment and the systems with calls of current : relay, engines, solenoid valves, automats, sound devices of alarm …with their permanent electrical circuits of monitoring, indication, control and operation.

The Poweris ELT packs make safe the whole systems at mains failure. The « charger unit » supplies the permanent equipment and charges the batteries.

The batteries lead seals associated provide at cuts sector the necessary energy for the release of power devices.

Advantages

  • Small overall dimensions facilitate its installation
  • A robust charger unit, secondary switch mode technology, adapted to the difficult industrial environments, supplemented effective protections increase its reliability
  • An output protected and dimensioned for 16Amps
  • Factory set for batteries lead seals simplifies its maintenance
  • A clear indication (three indicators and a report alarm on the charger unit) and a good accessibility give fast maintenance.

Standards

  • Complies to LV n°2006/95/CE - NF EN 60439-1
  • Complies to ECM n°2004/108/CE - NF EN 61000-6-2/NFEN 61000-6-4
  • Transformers comply to NF EN 61558-2-6 ou NF EN 61558-2-17

Characteristics

  • Mains inputs voltage : 230Vac - 10% +20% - 50/60Hz
  • Nominal output voltage : 12 - 24 or 48Vdc -15% +12,5%
  • Nominal output current In (A) : 12 and 24V : 5A - 48V : 2,5A
  • Short circuit current limitation : from In to In +5%
  • Nominal output power : 50 to 120W (at mains on) - 50 to 500W (at mains off)
  • Ripple output voltage : < 1% rms
  • Switching frequency : 100KHz (secondary)
  • Alarm relay : 1,25A – 125V (DC : 30W and AC : 50VA)
  • Ambient operating temperature : - 5 à + 50 °C
  • Storage temperature : - 45 à + 85 °C
  • Cooling system : natural cooling
  • Relative humidity : < 95% with 20°C ("all climates")
  • Degree of protection : IP 31 (in casing)
  • Dimensions : H 263 x W 270 x D 170 mm  (casing and chassis)
  • Weight : 9 to 19kg (according to the models with batteries)

    Indication (on the « charger unit ») :
  • LED signals : Mains on, Low and high DC voltage « mM »
  • Report alarm : Synthesis defects output voltage « mM »

Download

Brochure / Placa Plaquette / Brochure