CN.D chargers are designed to charge 12V to 48Vdc battery or maintain larger battery used for Genset starter or fire pumps Self.

They can also be integrated in box to provide power supplies with backup for process control systems, or to LV/MV switchgears.

Advantages

  • A robust charger batteries unit, secondary switch mode technology, adapted to the difficult industrial environments, supplemented effective protections increase its reliability
  • Charger units for integration in cabinet providing performances and data with high quality level (regulation, reliability, short circuit proof..)
  • A clear indication (three indicators and a report alarm) and a good accessibility give fast maintenance
  • Small overall dimensions facilitate its integration
  • Second voltage (Egalisation mode) for electrolytic cells batteries (Pb open and CdNi).

Standards

  • Complies to ECM n°2004/108/CE - NF EN 61000-6-2 / NF EN 61000-6-4
  • Complies to LV n°2006/95/CE - NF EN 60439-1
  • Transformers comply to NF EN 61558-2-6

Characteristics

  • Mains inputs voltage : 230 - 400Vac single phase - 10% +15% - 50Hz & - 10% +25% - 60Hz
  • Nominal charger voltage : 12 - 24 or 48Vdc, -15% +12,5%
  • Nominal charger current In (A) : 12Vdc : 12A - 24Vdc : 8 / 10 / 12 / 15A – 48Vdc : 5A
  • Short circuit current limitation : from 0,75 x In to In
  • Nominal charger power : 240 to 720W (at mains on)
  • Ripple output voltage : < 1% rms
  • Filtering : < 6% battery disconnected
  • Ambient operating temperature : - 5 to + 50 °C
  • Storage temperature : - 40 to + 50 °C
  • Cooling system : natural cooling
  • Relative humidity : < 95% with 20°C ("all climates")
  • Indication LED signals : « Mains » on, « Egalisation mode » on