DC Power

Battery charger in cabinet

Jupiter

The battery thyristors chargers Jupiter 500 serie are designed for a very large purpose : Telecom, Radio, Process etc.

This range is made up of wall-mont and rack modules which can be used in parallel in order to obtain the total power required by an application.

Advantages

- Chargers can be used in parallel from 1 to n in the same cabinet.
- Easy to install : wall-mount, bottom cable entry
- Rack mount version with plug-in connectors at the back
- Efficient filtering (EN 55022 & EN 55011class B) compatible with most sensible applications.
- Totally protected (input, output).
- Able to supply high permanent current with high peak current capacity (200% x Is max.).
- Straight display : LCD & LED indicators on the front panel ease the diagnosis.
- Default reported on dry contact.

Standards

- Complies to LV n° 93/68/CEE (NF EN60950)
- Complies to EMC 89/336/CEE (NF EN55022, NF EN61000)

Characteristics

- Input : 230Vac + 10%, - 15% - 47/63Hz
- Output : 24Vdc regulate to 1% Rms - 48Vdc regulate to 80mV Rms of In (adjustable)
- Nominal power : 230W to 1,5kW
- Nominal output current : 24V : 16 – 25 - 30A - 48V : 10 - 16 – 25 - 30A
- Battery current limitation : adjustable from 10 to 100 % of In
- Charger current limitation : 105% x In

- Power factor with PFC : > 0,99
- Static regulation : < 0,5% at Pn

- Ambient operating temperature : 0 to + 45 °C
- Storage temperature : - 40 to + 80 °C
- Relative humidity : < 95% with 20°C
- Degree of protection : IP 20

- Wall-mount dimensions : W 460 x H 350 x D 200 mm